Journal of Appliance Science & Technology ›› 2023, Vol. 0 ›› Issue (1): 40-44.doi: 10.19784/j.cnki.issn1672-0172.2023.01.005

• Articles • Previous Articles     Next Articles

Experimental study on non frost effect of air source heat pump

LI Huiling, ZHOU Hongliang, TANG Qixiong, MIAO Xiongwei   

  1. Guangdong Midea Refrigeration Equipment Co., Ltd. Foshan 528311
  • Online:2023-02-01 Published:2023-04-24

Abstract: By setting the temperature fluctuation of 3 P environment simulation room within 2℃ as the goal to achieve the effect of "no effect frost", the paraffin with phase change temperature of 46℃ is selected as the heat storage material, and the heat accumulator in line with the outer space of 3 P air conditioner is designed by theoretical calculation. Through experimental verification, the room temperature fluctuation, air outlet temperature and 24 h continuous heating operation attenuation of the heat storage defrosting system are analyzed. Compared with the traditional reverse defrosting system, the outdoor defrosting temperature fluctuation at 2℃ is compared. The experiment shows that the temperature fluctuation of the thermal storage defrosting system at 2℃ is as low as 1℃, significantly lower than 5.67℃ of the traditional reverse defrosting system, and the minimum air outlet temperature of the thermal storage defrosting system is above 39.1℃, which can meet the 24 h long-time operation and the fluctuation is less than 1℃.

Key words: Variable frequency air conditioner, Temperature fluctuation, Heat storage and defrosting, Continuous operation, Air outlet temperature