R290家用空调系统能效优化分析

任凤, 陈开东, 熊军, 高旭, 叶海森, 刘继胜   

  1. TCL空调器(中山)有限公司 广东中山 528427
  • 发布日期:2025-12-30
  • 作者简介:任凤,硕士学位。研究方向:R290家用空调应用研究。地址:广东省中山市南头镇TCL空调器(中山)有限公司。E-mail:2205031891@qq.com。

Energy efficiency optimization analysis of room air conditioner with refrigerant R290

REN Feng, CHEN Kaidong, XIONG Jun, GAO Xu, YE Haisen, LIU Jisheng   

  1. TCL Air Conditioner (Zhongshan) Co., Ltd. Zhongshan 528427
  • Published:2025-12-30

摘要: 目前市场上虽已有R290空调相关产品,但其能效(APF)还存在提升空间。本研究在1.5匹R32家用壁挂式空调基础上更换R290制冷剂,通过仿真与实验对其换热系统进行优化,进一步提高能效。首先,对样机制冷剂最佳充注量进行了测试,结果表明充注量为300 g时系统性能最优,APF达到4.812,且该充注量满足规范最大充注量要求。其次,测试发现,在进行制冷剂替换时,由于特性不同,需注意以下两方面:(1)R290制冷剂对分配器分流效果要求更高,通过优化内外机分配器,可在很大程度上改善换热器分流不均问题;(2)R290制冷剂对压降敏感,通过取消过冷段与更换连接管可有效降低系统压降。优化后样机APF提升5.84%,达到国标一级能效水平。

关键词: R290, 家用空调, 系统优化, 能效

Abstract: Although there are already products on the market using R290, there is room to improve its annual performance factor(APF). Optimizes the heat exchange system of a 1.5-horsepower R32 household wall mounted air conditioner using R290 refrigerant as substitute to improve its energy efficiency through simulation and experimentation. Firstly, the optimal refrigerant filling amount was tested. The results showed that the system had the best performance when the filling amount was 300 g, with APF of the system reaching 4.812, and the filling amount met the maximum filling amount requirements of the specifications. Secondly, through testing, it was found that when replacing R32 with R290 refrigerant, there were two aspects that need special attention due to different characteristics of the refrigerants: (1) R290 refrigerant had higher requirements for the distribution effect of the distributor, and the problem of uneven distribution in the heat exchanger could be greatly improved by optimizing the distributors of internal and external unit; (2) R290 refrigerant was sensitive to pressure drop. By eliminating the subcooling section and replacing the connecting pipe, the system pressure drop could be effectively reduced. The APF of the prototype increased by 5.84% after optimization, reaching first level of the energy efficiency of national standard.

Key words: R290, Room air conditioner, System optimization, Energy efficiency