  • Online:2024-10-01 Published:2024-10-16

摘要: 通过实验对比研究了R-410A和R-454B在管道机中的最优充注量及二者在AfullBfull工况下各性能参数的差异,并分析了在管道机中利用R-454B批量替换R-410A的可行性。结果表明:R-410A和R-454B最优充注量分别为3 kg和3.65 kg。与R-410A相比,R-454B在AfullBfull工况下能力分别降低2.22%和2.64%,EER2分别提升2.76%和1.41%,排气温度分别降低3.9 ℃和4.7 ℃,回气温度分别降低6.0 ℃和5.2 ℃,冷凝压力分别降低6.35%和5.70%,蒸发压力分别降低2.10%和2.14%。说明R-454B基本可满足目前R-410A系统的能力能效要求,且R-454B对系统部件高温保护要求和强度要求均低于R-410A,R-454B可直接使用目前R-410A的系统,为管道机批量切换制冷剂做出参考。

关键词: R-410A, R-454B, GWP, 性能, 制冷剂, EER2

Abstract: The optimal charge amounts of R-410A and R-454B in Air Handler Unit (AHU) were compared through experimental studies, and the differences in various performance parameters under Afull and Bfull conditions were analyzed. The feasibility of replacing R-410A with R-454B in AHU was also assessed. The results indicated that the optimal charge amounts for R-410A and R-454B are 3 kg and 3.65 kg, respectively. Compared to R-410A, R-454B showed a capacity reduction of 2.22% and 2.64% under Afull and Bfull conditions, respectively, with an EER2 increase of 2.76% and 1.41%. Additionally, the discharge temperature decreased by 3.9 °C and 4.7 °C, the suction temperature decreased by 6.0 °C and 5.2 °C, the condensing pressure decreased by 6.35% and 5.70%, and the evaporating pressure decreased by 2.10% and 2.14% under the same conditions. These results suggest that R-454B can generally meet the capacity and energy efficiency requirements of current R-410A systems. Moreover, R-454B imposes lower high-temperature protection and strength requirements on system components compared to R-410A, indicating that R-454B can be directly used in existing R-410A systems, a reference for the mass transition of refrigerants in AHU was provided.

Key words: R-410A, R-454B, GWP, Performance, Refrigerant, EER2