家电科技 ›› 2024, Vol. 0 ›› Issue (zk): 282-286.doi: 10.19784/j.cnki.issn1672-0172.2024.99.057

• 第二部分 制冷与空调 • 上一篇    下一篇

建筑气密性对不同机械通风系统换气效果的影响研究

赵强1,2, 刘德昌1,2, 袁淼2,3, 武凤玲1,2, 魏伟1,2   

  1. 1.青岛海尔智能技术研发有限公司 山东青岛 266101;
    2.数字家庭网络国家工程研究中心 山东青岛 266101;
    3.青岛海尔空调器有限总公司 山东青岛 266101
  • 出版日期:2024-12-10 发布日期:2024-12-31
  • 作者简介:赵强,博士学位。研究方向:室内空气健康。地址:山东省青岛市海尔路1号。E-mail:zhaoqiang01@haier.com。
  • 基金资助:
    山东省博士后创新人才支持计划(SDBX2022036)

Influence of building air tightness on the ventilation performance of different mechanical ventilation systems

ZHAO Qiang1,2, LIU Dechang1, YUAN Miao2,3, WU Fengling1, WEI Wei1   

  1. 1. Qingdao Haier Smart Technology R&D Co., Ltd., Qingdao 266101;
    2. National Engineering Research Center of Digital Home Networking. Qingdao 266101;
    3. Qingdao Haier Air Conditioner Co., Ltd., Qingdao 266101
  • Online:2024-12-10 Published:2024-12-31

摘要: 机械通风是一种可以有效控制进入室内的空气数量和品质的通风换气方式,建筑气密性是影响其通风换气性能的关键因素。本研究利用二氧化碳作为示踪气体,探究了不同建筑气密性条件下单向和双向通风系统对室内CO2浓度的衰减效果,结果表明,对于单向通风系统来说,房间气密性直接决定其通风效果,在一定的房间气密性条件下,存在一个最优的设计通风风量,在该最优风量以下,提高风量对于提升换气效果有较大的影响。对于双向新风系统,通风效果主要取决于气密性与进-出风风量参数的耦合,通过优化风量参数,可以在不同气密性的房间实现同样的换气效果。研究明确了建筑气密性对不同机械通风系统效果的影响,为机械通风系统的设计和优化提供了理论指导。

关键词: 建筑气密性, 机械通风, 换气效果, 二氧化碳

Abstract: Mechanical ventilation could effectively manipulate the air quantity and quality that enter the room, while building air tightness is the key factor affecting its ventilation performance. This study utilized carbon dioxide as a tracer gas and investigated the removal effect of unidirectional and bidirectional ventilation systems on indoor CO2 under different building air tightness conditions. The experimental results shou that room air tightness directly determines its ventilation effect for unidirectional ventilation system. Under a certain room air tightness, there is an optimal design ventilation volume, below which increasing the air volume has a greater impact on improving the ventilation effect. When the air volume is higher than this, the ventilation effect is less improved by continuing to increase the air volume. For bidirectional ventilation system, the ventilation effect mainly depends on the coupling of air tightness with input-outlet air volume parameters. By optimizing the air volume parameters, the same air exchange effect could be achieved in rooms with different air tightness. To sum up, the influence of building air tightness on the performance of different mechanical ventilation systems is studied, which provides theoretical guidance for the design and optimization of mechanical ventilation systems.

Key words: Building air tightness, Mechanical ventilation, Ventilation performance, Carbon dioxide

中图分类号: